Below you will find all pages of the AirLynk web browser as well as their functions. To connect to the AirLynk via web browser:
1. Connect the PC via the Ethernet Port
- Connect a CAT5 Ethernet cable (Straight through or Cross-over) from PC to BACnet on AirLynk panel.
- The Default IP Address of PLC is 192.168.1.100, Subnet mask is 255.255.255.0. If the PC and PLC are on different IP Networks, assign a static IP Address to the PC on the 192.168.1.xxx network.
- For instructions on how to navigate your operating system, to set up an IP address, and subnet mask contact your system administrator.
2. Connecting to Web Configurator
- After Setting your PC to be on the same subnet as the PLC (Instruction 1. Connect to PC), open a web browser on your PC and enter the IP address of the PLC; the default address is 192.168.1.100
- If the IP address of the PLC has been changed by a previous configuration, you will need to get the assigned IP address from display (Page 11 of the AirLynk Manual, Main Page 2 Curr IP).
AllFan
All Fan Command - Set speed and direction and check the “Send The All Fan Command” box to send the “All Fan Command”.
All Fan Fault Reset - Check the box to reset the faults of fans, if any. The “Faults Resetting” will change to 1 when actively resetting faults and 0 when it is done.
Fan Scanning - Is checked when the AirLynk is first powered on and will stay checked until the scan is complete.
FanControl
Fan Command - Fan selected is the fan that you want to work with for this whole page. Set the speed and direction and hit the “Send Fan Command” to send the command (you might need to check speed and direction to something different, send command, then change it back and send command again.)
Fan Settings - The only thing that applies here is the “Reset Fan Fault” checkbox. Everything else is for information purposes. “Reset Fan Fault” will uncheck when the fault process is run. “Fan Output” is scaled at 0.1 so a value of 123 would be 12.3.
Fan Diameter Changes - you must check “Enable Fan Diameter Changes” to be able to change the fan diameter. Once checked, it will only be enabled for 30 min. Select the correct diameter and hit “Set Blade Size”. Wait for it to uncheck before going to the next fan.
Motor Calibration - Select “Calibrate Motor” checkbox to calibrate the motor. Once it unchecks and the “Calibrate Motor Successful” checks, the motor calibration was successful, otherwise it failed. Note: AVDX and AVD SD only.
GroupControl
Group Control - Runs the selected group at the desired speed and direction. Select the group number you want to run and check the “Send Group Command” to run that group (see page 24 for group setup).
FanInfo (Faults, Drive Output, Fan Com Status, Message Counts)
The top of the “Fan Settings” web page is shown in image above. Scroll down on the AirLynk web browser to find the following additional information:
Faults - shows each fan’s faults. Note: If “Read Status” is checked, fault values will be “Fan Status” and not faults.
Drive Output - shows each fan’s output at a scale of 0.1. Schneider drives are frequency output, some older models have RPM output.
Fan Com Status - displays 1 if the AirLynk is communicating to the fan.
Message Counts - displays the messages sent by the AirLynk and the messages received by the AirLynk. Check the “Reset Message Counts” to reset all counts to 0 (should be done before checking for error counts for the first time.)
Network
Fan Enabled - Fan type set here will always pull into the AirLynk regardless of if there is a fan at that address or not. Fans pulled in here that don’t exist will cause the AirLynk to operate slowly.
Group Setup
Select what group you want to add and remove fans to by checking/unchecking the fans from the “Select Fans in Group” list. Check the “Save Group” to save the group.
Schedule Setup
Used for scheduling days, start time, end time, speed, and direction of the fans/groups to run. Check “Save Schedule” to save the schedule.
AirEffect
Sets up use of AirEffect (refer to AirEffect Manual).
FanDistance
Used for AirEffect (refer to AirEffect Manual).
MB Read/Write (Call MacroAir For Password) (2 different pages)
Used only when on the phone with MacroAir Technical Support. Read and write directly to the fan through modbus.
Address- fan address
Register- register you want to change
Value- the value you want to send to the fan or the value read.
Write/Read Value- sends the requested read/write.
Error message- 0 is no issue, read/write successful
PassChange (password)
Changes the default admin user and password, check “Set User and Password” to set.
Only used to access the web browsers, can only be reset back to admin/admin through a PLC update.
Set Time (password)
Actual Date And Time: Displays the current date and time.
Set Time and Date: Used in scheduling. Check “Set Time And Date” to set it to the PLC.
Set Time and Set Date: Used to set the desired time and date.
Days of the week: 0 = Sunday, 1 = Monday, etc. to 6 = Saturday.
Set BBMD
Used in some BMS systems to access it out of network.